Amps to KVA Converter 3 Phase

Calculate three-phase kVA using line-to-line or line-to-neutral voltage.

Enter values

Live calculation
A
V

Result

Ready
Active formula

Enter positive values to calculate.

How Amps to KVA Converter 3 Phase Works

To convert amps to kVA in a three-phase system, identify the voltage measurement type (line-to-line or line-to-neutral) and apply the matching formula. The converter handles both measurement types automatically.

1

Select the voltage measurement type

Choose line-to-line voltage or line-to-neutral voltage. Line-to-line voltage measures between two phase conductors. Line-to-neutral voltage measures between one phase conductor and the neutral point.

2

Enter the current and voltage values

Type the current in amperes (A) and the voltage in volts (V). Use the values from the equipment nameplate or a calibrated multimeter reading.

3

Read the three-phase kVA result

The converter multiplies current, voltage, and the three-phase multiplier, then divides by 1,000 to produce kilovolt-amperes (kVA). The active formula and breakdown appear in the result panel.

Three-phase systems use √3 (1.732) for line-to-line voltage and 3 for line-to-neutral voltage. Selecting the wrong voltage type produces an incorrect kVA result.

Amps to KVA 3 Phase Formula

Two formulas convert amps to kVA in a three-phase circuit, based on the voltage measurement type.

Line-to-line voltage

kVA = (√3 × Amps × VLL) ÷ 1,000

Multiply 1.732 by the current in amps and the line-to-line voltage in volts, then divide by 1,000.

Line-to-neutral voltage

kVA = (3 × Amps × VLN) ÷ 1,000

Multiply 3 by the current in amps and the line-to-neutral voltage in volts, then divide by 1,000.

Worked examples

100 A at 415 V line-to-line

kVA = 1.732 × 100 × 415 ÷ 1,000 = 71.878 kVA

100 A at 240 V line-to-neutral

kVA = 3 × 100 × 240 ÷ 1,000 = 72 kVA

Amps to KVA 3 Phase Conversion Chart

Pre-calculated three-phase kVA values for common amperage and line-to-line voltage combinations using the formula kVA = (√3 × A × V) ÷ 1,000.

Three-phase kVA — line-to-line voltage

AmpskVA @ 208 VkVA @ 220 VkVA @ 380 VkVA @ 400 VkVA @ 415 VkVA @ 480 V
10 A3.603.816.586.937.198.31
15 A5.405.729.8710.3910.7812.47
20 A7.217.6213.1613.8614.3816.63
30 A10.8111.4319.7520.7821.5624.94
50 A18.0219.0532.9134.6435.9441.57
80 A28.8330.4852.6655.4257.5066.51
100 A36.0338.1165.8269.2871.8883.14
150 A54.0557.1698.73103.92107.82124.71
200 A72.0776.21131.64138.56143.76166.28
400 A144.14152.42263.28277.13287.51332.55

All values assume a balanced three-phase load and use √3 (1.732) as the multiplier. Actual kVA depends on power factor and load balance.