All calculators

KVA to Amps UK

Convert kVA to current using common UK 230 V and 400 V supplies.

Enter values

Live calculation
kVA

Result

Ready
Active formula—
—

Enter positive values to calculate.

How KVA to Amps UK Works

To convert kVA to amps in the UK, select the supply type (single-phase 230 V or three-phase 400 V) and enter the apparent power in kVA. The calculator returns the current in amperes.

1

Select the UK supply type

UK single-phase supplies run at 230 V (nominal). UK three-phase supplies run at 400 V line-to-line. These are the standard voltages defined by BS 7671 wiring regulations.

2

Enter the apparent power in kVA

Type the kVA rating from the transformer nameplate, generator specification sheet, or UPS data plate.

3

Read the current in amps

Single-phase uses A = (kVA × 1,000) ÷ 230. Three-phase uses A = (kVA × 1,000) ÷ (√3 × 400). The calculator shows the full formula breakdown in the result panel.

UK nominal voltages are 230 V (single-phase) and 400 V (three-phase), per BS EN 50160. Actual supply voltage ranges from 216.2 V to 253 V for single-phase.

KVA to Amps UK Formula

Two formulas convert kVA to amps for UK electrical supplies, based on the phase configuration.

UK single-phase · 230 V

Amps = (kVA × 1,000) ÷ 230

Multiply the kVA value by 1,000, then divide by 230.

UK three-phase · 400 V

Amps = (kVA × 1,000) ÷ (√3 × 400)

Multiply the kVA value by 1,000, then divide by 1.732 × 400 (692.8).

Worked examples

10 kVA single-phase UK

A = 10 × 1,000 ÷ 230 = 43.48 A

100 kVA three-phase UK

A = 100 × 1,000 ÷ (1.732 × 400) = 144.34 A

KVA to Amps UK Conversion Chart

Pre-calculated amperage values for common kVA ratings at UK standard voltages of 230 V (single-phase) and 400 V (three-phase).

KVA to Amps — UK 230 V and 400 V

kVAAmps @ 230 V (1Ø)Amps @ 400 V (3Ø)
1 kVA4.351.44
2.5 kVA10.873.61
5 kVA21.747.22
10 kVA43.4814.43
15 kVA65.2221.65
25 kVA108.7036.08
50 kVA217.3972.17
100 kVA434.78144.34
200 kVA869.57288.68
500 kVA2,173.91721.69

Single-phase: A = (kVA × 1,000) ÷ 230. Three-phase: A = (kVA × 1,000) ÷ (1.732 × 400). All values assume nominal UK voltage levels per BS EN 50160.