All calculators

KVA to Amps UK

Convert kVA to current using common UK 230 V and 400 V supplies.

Enter values

Live calculation
kVA

Result

Ready
Active formula

Enter positive values to calculate.

How KVA to Amps UK Works

To convert kVA to amps in the UK, select the supply type (single-phase 230 V or three-phase 400 V) and enter the apparent power in kVA. The calculator returns the current in amperes.

1

Select the UK supply type

UK single-phase supplies run at 230 V (nominal). UK three-phase supplies run at 400 V line-to-line. These are the standard voltages defined by BS 7671 wiring regulations.

2

Enter the apparent power in kVA

Type the kVA rating from the transformer nameplate, generator specification sheet, or UPS data plate.

3

Read the current in amps

Single-phase uses A = (kVA × 1,000) ÷ 230. Three-phase uses A = (kVA × 1,000) ÷ (√3 × 400). The calculator shows the full formula breakdown in the result panel.

UK nominal voltages are 230 V (single-phase) and 400 V (three-phase), per BS EN 50160. Actual supply voltage ranges from 216.2 V to 253 V for single-phase.

KVA to Amps UK Formula

Two formulas convert kVA to amps for UK electrical supplies, based on the phase configuration.

UK single-phase · 230 V

Amps = (kVA × 1,000) ÷ 230

Multiply the kVA value by 1,000, then divide by 230.

UK three-phase · 400 V

Amps = (kVA × 1,000) ÷ (√3 × 400)

Multiply the kVA value by 1,000, then divide by 1.732 × 400 (692.8).

Worked examples

10 kVA single-phase UK

A = 10 × 1,000 ÷ 230 = 43.48 A

100 kVA three-phase UK

A = 100 × 1,000 ÷ (1.732 × 400) = 144.34 A

KVA to Amps UK Conversion Chart

Pre-calculated amperage values for common kVA ratings at UK standard voltages of 230 V (single-phase) and 400 V (three-phase).

KVA to Amps — UK 230 V and 400 V

kVAAmps @ 230 V (1Ø)Amps @ 400 V (3Ø)
1 kVA4.351.44
2.5 kVA10.873.61
5 kVA21.747.22
10 kVA43.4814.43
15 kVA65.2221.65
25 kVA108.7036.08
50 kVA217.3972.17
100 kVA434.78144.34
200 kVA869.57288.68
500 kVA2,173.91721.69

Single-phase: A = (kVA × 1,000) ÷ 230. Three-phase: A = (kVA × 1,000) ÷ (1.732 × 400). All values assume nominal UK voltage levels per BS EN 50160.